TOHO TOHO ELECTRONICS INC.
DWG. No.
45-4199-E
PAGE
47/66
Character
PV screen
Auxiliary screen
Designation Description Initial value
27

ch

Set the main
output operation
amount change
limiter to rise
Setting range: 0.0 to 120.0
Setting unit: %/sampling cycle

28

ch

Set the main
output operation
amount change
limiter to fall
Setting range: 0.0 to 120.0
Setting unit: %/sampling cycle

29

ch

Set for a main
output abnormality
Setting range: 0.0 to 100.0 (-10.0 to -110.0: in analog
output)
Setting unit: %

30

ch

Auxiliary output
operation amount
Used to monitor the auxiliary output operation amount
and to set the operation amount in manual control.
In automatic control
Display range: 0.0 to 100.0 (-10.0 to -110.0: in analog
output)
Display unit: %
In manual control
Setting range: Lower limit to the upper limit for the
operation amount limiter
Setting unit: %

31

ch

Set a proportional
band for the
auxiliary output
Setting range: 0.00 to 10.00
Setting unit: Magnification with regard to the
proportional band for the main output

32

ch

Set a proportional
cycle for the
auxiliary output
Setting range: 1 to 120 seconds

33

ch

Set an upper limit
for the auxiliary
output operation
amount limiter
Setting range: Set a lower limit for the operation amount
limiter to 100.0 (-110.0: in analog output)
Setting unit: %

34

ch

Set a lower limit
for the auxiliary
output operation
amount limiter
Setting range: Set the system to 0.0 (-10.0: in analog
output) to an upper limit for the operation
amount limiter
Setting unit: %

35

ch

Set the auxiliary
output operation
amount change
limiter to rise
Setting range: 0.0 to 120.0
Setting unit: %/sampling cycle

36

ch

Set the auxiliary
output operation
amount change
limiter to fall
Setting range: 0.0 to 120.0
Setting unit: %/sampling cycle

37

ch

Set for an auxiliary
output abnormality
Setting range: 0.0 to 100.0 (-10.0 to -110.0: in analog
output)
Setting unit: %
