TOHO TOHO ELECTRONICS INC.
DWG. No.
45-4199-E
PAGE
45/66
Character
PV screen
Auxiliary screen
Designation Description Initial value
13

ch

Set a control type Timer connection channel

: Unrelated to the timer

: The timer starts/stops control.
Control operation

: TYPE A

: TYPE B (overshoot inhibition function)
Main output control type

: PID control

: ON/OFF control

: Cascade control (CH2 only)

: Remote control (CH2 and only when the
input type is between

and

)
Type of auxiliary output control

: Disabled

: PID

: ON/OFF

14

ch

Set forward/
reverse action
switchover
: Reverse action
: Forward action
15

ch

Main output
operation amount
Used to monitor the main output operation amount and
to set the operation amount in manual control.
In automatic control
Display range: 0.0 to 100.0 (-10.0 to -110.0: in analog
output)
Display unit: %
In manual control
Setting range: Lower limit to the upper limit for the
operation amount limiter
Setting unit: %

16

ch

Set a tuning type
: Auto-tuning (output 1)
: Self-tuning (output 1)
: Auto-tuning (output 2)
: Self-tuning (output 2)
: Auto-tuning (output 1, output 2)
Select
/
/
and press the FUNC 1 key to start the
auto-tuning.
Press the FUNC 1 key during the auto-tuning to release
it.
17

ch

Set an AT factor Setting range: 0.1 to 10.00
Setting unit: Times
