6.8 Composition of an ASCII request message
(transmitted from a high-level computer to this product)
For the codes a) through g), see "6.10 Description of ASCII codes."
6.8.1 Composition of a read request message
a)
Start code
“:”
b)
Slave address
“1” , “B”
c)
Function code
“0” , “3”
d)
Register address
High level
“0” , “0”
First register address
Low level
“0” , “0”
e)
Number of registers
High level
“0” ,
“0”
Fixed at 2
Low level
“0” , “2”
f)
LRC
“E” , “0”
g)
End code
CR, LF
6.8.2 Composition of a write request message
a)
Start code
“:”
b)
Slave address
“0” , “3”
c)
Function code
“1” , “0”
d)
Register address
High level
“0” , “0”
First register address
Low level
“C” , “0”
e)
Number of registers
High level
“0” , “0”
Fixed at 2
Low level
“0” , “2”
h)
Number of data items
“0” , “4”
Number of registers
2
i)
Data for the first register
(a low-level word)
High level
“0” , “0”
When writing
,
,
, and
H in the data, write them in the
order described on the left-hand
side. ( represents 1 byte.)
Low level
“6” , “F”
Data for the first register + 1
(a high-level word)
High level
“0” , “0”
Low level
“0” , “0”
f)
LRC
“E” , “0”
g)
End code
CR, LF