Toho-electronics TRM-006A Manual de usuario Pagina 18

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 40
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 17
18
5.2 Setting a data length
5.3 Setting a stop bit length
5.4 Setting a parity
5.5 Setting a BCC check
The BCC check is disabled.
Initial value of MODBUS (RTU):EcIInitial value of MODBUS (ASCII):EcI
^gfo
***
F
Stop bit 1
I
Stop bit 2
c
f
Odd parity
D
Even parity
N
Data length, 7 bits
E
Data length, 8 bits
* The RTU mode settings come only in three types:
H
H
.
The ASCII mode settings come only in three types:
H
H
.
5.6 Setting a communications speed
While in the "Set a communications speed" screen on the preceding page, operate the and
keys to make the settings. The initial value is HH.
^jTL
****
I
1200 BPS
K
2400 BPS
E
4800 BPS
M
9600 BPS
FI
19200 BPS
5.7 Setting an address
While in the "Set a communications address" screen on the preceding page, operate the and
keys to make the settings. The initial value is H.
^idh
F
Setting range: 1 to 247 stations (It cannot be set to a 0.)
Vista de pagina 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 39 40

Comentarios a estos manuales

Sin comentarios