7.9.12 Examples of communications to be written
Example: Request message: Requests that the temperature alarm output setting of EIF in channel 1
(High-level computer) of unit number 3 be changed to deviation top/bottom alarm + holding.
In response to that,
Response message: This returns a notice that the request message has been received.
(This product) *Check that it has been correctly written by reading the data separately.
Write request message (transmitted from a high-level computer)
S
T
X
3
1
W
E
1
F
0
0
0
1
1
E
T
X
B
C
C
―⑤― ―――⑥―――
Response message (returned from this product)
S
T
X
3
1
A
C
K
E
T
X
B
C
C
Code Code, data ASCII code, note 2)
Start code STX 02H
Unit number 3 33H
Channel number 1 31H
Request contents W (Write) 57H
Identifier, note 1) E1F 41H 34H 46H
Numerical data 00011 30H 30H 30H 31H 31H
End code ETX 03H
BCC data request 56H
response 05H
Acknowledge code ACK 06H
Note 1): See "6. Table of identifiers (codes)."
Note 2): For the ASCII codes, see "7.9.13. Table of ASCII codes."