- 30 -
15 pcs RUN,OUT,EV1,EV2,EV3,EV4、TS1,TS2,TS3,TS4,TIME,AUTO,MAN
U,AT,END
Accuracy of
Indication /Set
ting
Thermocouples of K, J, T, E, R, S, B and N
Either larger ± (0.3 % + 1 digit) or ± 2 °C of the indicated value
Note: ± 3 °C for -100 to 0 °C and ± 4 °C for -200 to -100 °C
No specification for 400 °C or lower for B thermocouple
* In standard environment conditions (23 ± 10 °C)
Thermocouples of U and L:
Either larger ± (0.3 % + 1 digit) or ± 4 °C of the indicated value
± 6 °C for 0 °C or lower
WRe 5-26
Either larger ± (0.6 % + 1 digit) or ± 4 °C of the indicated value
PR 40-20
± 9.4 °C ± 1 digit No accuracy specified for lower than 800 °C
PL II
Either larger ± (0.3 % + 1 digit) or ± 2 °C of the indicated value
Either larger ± (0.3 % + 1 digit) or ± 0.9 °C of the indicated value
* In standard environment conditions (23 ± 10 °C)
± 0.3 % ± 1 digit of FS * In standard environment conditions (23 ± 10 °
C)
Only 0-10mV, ± 0.5 % ± 1 digit of FS
± 0.3 % ± 1 digit of FS * In standard environment conditions (23 ± 10 °
C)
Set all parameters with the front keys.
Normal screen lock setting, Pattern No. setting mode lock setting, Alarm temperature setting mode lock setti
ng, PID setting mode lock setting ,26 kinds.
Select from ON/OFF control, PID control .
Relay contact output, SSR drive voltage output Approx. 4 sec output 0%.
4~20mA DC output Approx. 4 sec. 1mA output
Relay contact output, SSR drive voltage output : output: 0% output (output OFF)
4~20mA DC : output: 0%
Relay contact output : contact specification 1a contact capacity 250VAC 3A(resistance load).
SSR drive voltage output: OFF time; 0V DC ON time; 12V DC Loaded resistance over 600Ω.
(It may vary according to a calculation with SSR inner resistance.)
4~20mA DC output: Output current 4~20mA DC Loaded resistance below 600Ω.
Output range:DC2.4~21.6mA
Communication specification : TTL level
Network: point to point (1 vs 1 station)
Communication distance : Use TOHO loader cable.
Address : 1 - 99 stations
No. of patterns
No. of steps
No. of patterns 15max
No. of steps 99max * The maximum No. varies depending on the selected
(0.5% + 0.5 seconds) of setting time
0 - 99 times (0 for infinite number)
Wait zone : 0.0 to 999.9C Wait time : 0 to 99 hours 59 minutes
Relay contact output : contact specification 1a contact capacity 250VAC 1A(resistance load).
OFF time voltage: 6V DC ON time current: 6mA DC
Minimum input time: 200mSEC and over
Communication specification : RS-485
network : Multidrop(1:31)
Communication distance : 500 m
Address : 1 - 99 stations * For MODBUS setting, 1 - 247 stations