48-7009-E 5-74
5.6.3 Complementary explanation of the bank automatic switching function
Regarding the zone threshold* setting [PM1 to PM7]:
If all seven points at most are set with different values one another, eight zones can be established for each
temperature allowing eight banks to be used. The setting range is from SLL to SLH. If all seven points
are set to SLH, the threshold is integrated into one zone to provide the maximum value (applicable only for
the bank 0). The initial value is set to this status.
Note The threshold values are PM7 to PM1 in sequence from the largest. Changing the sequence is not
allowed. Therefore, a lower temperature should be set to a threshold with a smaller designation
number. (The system is constructed in such a way.)
The following is an example of the setting.
■ Setting example of the auto bank switching function setting mode (initial value: PM1 to PM7 1200)
The initial setting status is shown. The SLH is set for all PM1 to PM7. No auto switching is
performed.
PM1=PM2=PM3=PM4=PM5=PM6=PM7=SLH
SLH PM7
PM6
PM5
PM4
PM3
PM2
PM1
When one bank is used
(zone threshold: SLH for all initial values):
Bank 0 is fixed; no auto switching is performed.
Bank
auto-switching
source