Toho-electronics TTM200 Manual de usuario Pagina 159

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 264
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 158
48-7009-E 6-11
PV filter setting
SEt02
INP2
Setting content
Initial value
6
PdF2
0.0 to 99.9 (seconds)
0.0
The PV filter setting is a function that demonstrates the CR filter effect on software through performing a first-order lag
calculation for PV of the remote SV input.
The filter effect is set using the time constant [t].
(Time constant is defined as the time required for PV to reach about 63 % when an input changes in a step configuration.)
* CR filter --- a filter of first-order lag
Note Application of PV filter
(1) Effect of noise is alleviated due to elimination of high-frequency noise when electric noise applies on inputs.
(2) Response can be delayed against abrupt change of an input.
100%
0%
Time
100%
0%
Time
100%
0%
Time
63%
Time constant (t)
Input signal
Input read in
When no digital PV filter exists
[Time constant (t) = 0]
When a digital PV filter exists
[Time constant (t) > 0]
Local/remote switchover
SEt02
INP2
Setting content
Initial value
7
LR
0
Local
0
1
Remote 1 (scaling at SLL , SLH)
2
Remote 2 (scaling at FSL 2, FSH 2)
Vista de pagina 158
1 2 ... 154 155 156 157 158 159 160 161 162 163 164 ... 263 264

Comentarios a estos manuales

Sin comentarios