48-7009-E 4-29
4.2.10 Switchover to the ON/OFF control
The ON/OFF control is set in BANK 1 for the initial setting at factory shipment.
How to set the ON/OFF control is described.
Constant value run mode screen
PV value (present value)
SV value (target value)
Hold MODE key pressed for 2 seconds.
Input 1 setting screen
Each set screen
Each setting mode
Press the key three times.
Press it, however, twice for TTM-204.
Control setting mode
Press MODE key once.
S04-1 Bank setting mode
Hold MODE key pressed for 2 seconds.
* Setting change to the ON/OFF control is conducted in the bank setting screen.
Changing “0” to “1” using the key results in the setting of the ON/OFF control.
Then, holding the MODE key pressed for 2 seconds, the screen moves back to the operating mode screen.
(In about 2 minutes, the screen automatically moves back to the operating mode screen.)
* The sensitivity range for the ON/OFF control is set at 1 °C at factory shipment.
* Setting the ON/OFF control results in displaying no items related to the PID control.
For program run mode screen:
PV value (present value)
SV value (PRoG)
Hold MODE key pressed for 2 seconds
Setting mode is the same as that for constant
value run mode.
(To input 1 setting screen)