48-7009-E 6-81
Bank Automatic Switching Source Setting
Setting Contents
Initial
Value
2
bAS
Bank Automatic Switching Source Setting 3
00
Function
*0
Select SV value
*1
Select ramp SV value
*2
Select PV value
Control Mode Interlock Function
0*
All Mode
1*
RUN/MAN Mode Only
2*
RUN Mode Only
Select the source for the SV value to which the
Bank Automatic Switching will be done.
When SET04 bANKH=0, the setting will be
invalid.
There will be no indication either.
※2 Bank Automatic Switching Source Setting (bAS)
Select source to which the Bank Automatic Switching will be done. Switch the bank in accordance with
the source selected.
Setting RangeWhen 0, select SV Value Local and Remote (only Option Y)
When 1, select ramp SV value.
When 2, select PV value
NOTE: The behavior of AT (Auto-Tuning) when (bAF = 1).
Regardless of the source setting to which the Bank Automatic Switching will be done, it will select
SET04(SV). After the completion of the AT (Auto-Tuning), it will go back to Bank Automatic
Switching Source Setting (bAS).
In case the Zone ThresholdSetting (PM) is set, at the same time the parameter (P, I, D) is set to the
bank, the PID value obtained from the AT (Auto-Tuning) will be reflected to the Bank No. according to
the threshold.