48-7009-E 6-59
6.7 DI setting
■ DI function setting
Press the MODE key for making a setting effective (including reverse feed).
****
||||
|||+-- DI 1 setting (settable when an option existent)
||+--- DI 2 setting (settable when an option existent)
|+---- DI 3 setting (settable when an option existent)
+----- DI 4 setting (settable when an option existent)
When Constant operation
Mode
MD
When Program Mode
Start
When Constant operation
Mode
READY
When Program Mode
stop
Step Forward 3
(during program mode)
Pause 3
(during program mode)
Set the DI function.
0: No DI function
1: Bank switchover is executed.
Bank selection table per DI 1 state
The parameters change right after switchover when the bank is changed per DI.
2: <During Constant Operation Mode> Switching of Control Mode and STOP.
<During the Program Mode> Switching of In-Operation and Operation Stop.
3: Switching of AUTO & MANUAL is done
4: Switching of Output Movement (forward / reverse movement) is done.
5: The Star & Stop of Auto-Tuning of PID Control is done.
Maintain the DI to active condition until the auto-tuning is completed.
In case the operation is suspended half-way, the auto-tuning will stop.