<Forward operation>
Off-point CP2 = 0
C2
ON
OFF
PV
Low
SV
High
Off-point CP2 = positive value
C2
CP2
ON
OFF
A point
PV
Low
SV
High
Off-point CP2 = negative value
C2
CP2
ON
OFF
B point
PV
Low
SV
High
C2: Sensitivity setting
C2: Sensitivity setting
CP2: Off-point position
A point: SV + CP2
C2: Sensitivity setting
CP2: Off-point position
B point: SV - CP2
Secondary control protection timer
SEt04
CNt
Setting content
Initial value
53
Fdt2
Sub-control Protection off Timer 0 to 99 (minutes)
0
54
Ndt2
Sub-control Protection on Timer 0~99(min.) 3
0
BEHAVIOR DUINRG SUB-CONTROL PROTECTION OFF TIMER (Fdt2) SETTING
Setting value
Temperature
Control
output
Control
sensitivity
ON
OFF
Protection
timer