48-7009-E 6-36
Secondary control operating amount limiter upper limit
SEt04
CNt
Setting content
Initial value
42
MLH2
Digital output
MLL 2 to 100.0 (%)
100.0
Analog output
MLL 2 to 110.0 (%)
Set the secondary control operating amount limiter upper limit.
A limit is set for the upper limit of the operating amount calculated.
Output
Operating amount
limiter upper limit
50 %
100%
0%
Secondary control operating amount limiter lower limit
SEt04
CNt
Setting content
Initial value
43
MLL2
Digital output
0.0 to MLH 2 (%)
0.0
Analog output
-10.0 to MLH 2 (%)
Set the secondary control operating amount limiter lower limit.
A limit is set for the lower limit of the operating amount calculated.
Output
Operating amount
limiter lower limit
50 %
100%
0%