Primary control loop abnormality time setting
SEt04
CNt
Setting content
Initial value
32
LoP1
0 to 9999 (seconds)
0
Set the primary control loop abnormality time setting.
The function is to detect an abnormality in the control loop.
- The control loop anomaly PV change threshold is judged at each LoP1 time.
A loop abnormality is determined if each change threshold is judged to be equal to or below PS1.
For details, see section5.4.6 Loop abnormality function on pages 5-38 and 39.