Toho-electronics TTM200 Manual de usuario Pagina 221

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 264
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 220
48-7009-E 6-73
6.13 PROGRAM FUNCTION SETTING
Operation Type Setting
PGF
Setting Contents
Initial
Value
1
C/P
Operation Type Setting 3
0
0
Constant Operation Mode
1
Program Mode
※1 Operation Type Setting (C/P)
The program operation will take place when the Program Mode is set.
The Program Mode executes the program operation by automatically switching the Bank Function and
Program Step Function.
Setting Range
: Constant Operation Mode (Program Mode OFF)
: Program Mode (Program Mode ON)
Behavior during the Program Mode
STEP1 STEP2 STEP3 STEP4 STEP5 STEP6 STEP7 STEP8
SV1
50℃
TIM1
00:30
ST1BK
BANK1
BANK1
RMP
10
P1
4.0
o2F
20
5
SV2
100℃
TIM2
00:40
ST2BK
BANK1
BANK1
RMP
10
o2F
SV3
150℃
TIM3
00:50
ST3BK
BANK1
BANK1
RMP
10
o2F
SV4
200℃
TIM4
01:00
ST4BK
BANK1
BANK1
RMP
10
o2F
SV5
150℃
TIM5
00:30
ST5BK
BANK2
BANK2
RMP
5
o2F
TIMER ON
DELAY
SV6
100℃
TIM6
00:40
ST6BK
BANK2
BANK2
RMP
5
SV7
150℃
TIM7
00:50
ST7BK
BANK1
BANK1
RMP
10
o2F
SV8
20℃
TIM8
00:10
ST8BK
BANK3
BANK3
RMP
30
o2F
RUN OUT
BANK0
RMP
P1
3.0
MAX. 16 PARAMETER
o2F
END OUT
0
0
BANK0
RMP
o2F
END OUT
START
OPERATION
END
OPERATION
END
PV
BANK0
RMP
MAX
16パラメータ
o2F
END OUT
OPERATION
STOP
STOP
OPERATION
STOP OPERATION
P1
2.0
10
2
P1
3.0
0
0
P1
3.0
0
0
P1
4.0
20
5
P1
4.0
20
5
P1
4.0
20
5
P1
4.0
20
5
P1
2.0
10
2
P1
2.0
10
2
SET22
SETTING 
VALUE
MAX. 8 STEPS
SET20
SETTING
 VALUE
STEP V SETTING
STEP TIME SETTING
STEP BANK SETTING
o2F
TEMP. CHANGE PATTERN
REFER
1BANK
OPERATION
STOP
OUTPUT EXAMPLE
TIMER ON
DELAY
o2F